250 kW

Descarga de Documentos Técnicos
Ficha Técnica
Plano

 Gen Set model number
GSJD10250M
 Mechanical power
250
 kWe Standby range
243-254
 Engine manufacturer
JOHN DEERE
 Engine model number
6081HF001
 EPA / Tier
1
 Number of cylinders
6
 Disp. cu. in. (L)
496(8.1)
 Aspiration
Turbocharged
 BMEP psi (kpa)
368(2538)
 Engine CFM cfm (m^3/min)
749(21.2)
 Engine rated Hp (kWm)
413(308)
 RPM
1800
 Alternator manufacturer
MARATHON
 Alternator model number
432PSL6210
 Insulation system class
150 H
 Voltage
220/440/208/480V
 Voltage configuration
PARALLE LOW WYE
 Frequency (Hz)
60
 Number of phases
3
 Standby circuit breaker rating
821.1
410.5
868.4
376.3
 
 Generator's ratings for 150°C H Rise
 Standby kW
292
 Amps
959
480
1,014
440
 
 Engine ratings
 Standby kW
308
 Standby Amps
1011.6
506
1,070
464
 Prime kW
263
 Prime Amps
863.8
432
914
396

 
  Ventajas Competitivas
Plantas Eléctricas de 20 a 3000 kW
  Casetas Acústicas
  Sincronización y Transferencias
  Alternativas para el Ahorro de Energía
  Peak Shaving y Autogeneración

 

Contacto

Plantas Eléctricas
En México D.F.
(55) 5626-5392 y 2396
Larga Distancia Sin Costo 01-800-800-IGSA (4472)
ventasplantas@igsa.com.mx

Sincronía y Transferencia, Alternativas para ahorro y Peak Shaving
(55) 5626-5487
cesarrr@igsa.com.mx
proyectos@igsa.com.mx

Corporativo
Paseo de la Reforma 2977
Col. Cuajimalpa
C.P. 05000
México, D.F.

Planta Lerma
Carretera Amomoluco Ocoyoacac 5
Lerma, Estado de México
Tel.- (728) 287-7399 y (728) 287-7533

Guadalajara, Jalisco
Lázaro Cárdenas 2185
Col. Ferrocarril
C.P. 44440
Tel: (33) 3812-2389
3811-7721
3811-0951